Support Industrielle sensorer
Support Explosion Protection

Ikke tilgængelig for indkøb

This product has been replaced.Go to replacement product NJ5-18GM-N-10M
Ikke tilgængelig for indkøb
Ikke tilgængelig for indkøb

Inductive sensor NJ5-18GM-N-10M

NJ5-18GM-N-10M
  • Comfort series
  • 5 mm flush
  • Usable up to SIL 2 acc. to IEC 61508


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Uddrag af datablad: Tekniske data for   NJ5-18GM-N-10M

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance5 mm
Installationflush
Assured operating distance0 ... 4.05 mm
Reduction factor rAl 0.21
Reduction factor rCu 0.18
Reduction factor r304 0.63
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Operating voltage5 ... 25 V
Switching frequency0 ... 500 Hz
Hysteresis3 %
Current consumption
Measuring plate not detected≥ 3 mA at nominal voltage
Measuring plate detected≤ 1 mA at nominal voltage
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0037X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GaPTB 00 ATEX 2048 X
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
EAC conformityTR CU 012/2011
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0452
CSA approvalcCSAus Listed, General Purpose
CCC approval
Hazardous Location2020322315002255
NEPSI approval
NEPSI certificateGYJ16.1393X
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP66 / IP67
Cable
Cable diameter6 mm ± 0.2 mm
Bending radius> 10 x cable diameter
MaterialPVC
Core cross section0.75 mm2
Length10 m
Dimensions
Length40 mm
Diameter18 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ5-18GM-N-10M

Documents: NJ5-18GM-N-10M

Instruction manualsFil typeFil størrelse
ИнструкцииPDF191 KB
Návod k poużitíPDF181 KB
Instruktions manualPDF180 KB
Instruction manualPDF182 KB
KasutusjuhendPDF175 KB
KäyttöohjePDF174 KB
Manuel d'instructionsPDF186 KB
BetriebsanleitungPDF181 KB
Οδηγίες χρήσηςPDF193 KB
HandleidingPDF181 KB
Instruction manual / BetriebsanleitungPDF179 KB
Használati útmutatóPDF185 KB
Manuale di istruzioniPDF184 KB
Lietošanas pamācībaPDF181 KB
Instrukciju vadovasPDF182 KB
Instrukcja obsługiPDF184 KB
Manual de instruçõesPDF184 KB
Manual de utilizarePDF184 KB
Návod na poużitiePDF183 KB
Navodila za uporaboPDF179 KB
Manual de instruccionesPDF185 KB
ManualPDF179 KB
Technical information
Installation conditionsPDF1054 KB
EinbaubedingungenPDF1060 KB

CAD+CAE: NJ5-18GM-N-10M

CADFil typeFil størrelse
CAD 3-D / CAD 3-DSTP57 KB
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ66 KB

Tilhørende produkter: NJ5-18GM-N-10M

Accessories

Mounting flange, 18 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.